Home > New >

CSB HRL12330WFR CSB 12VDC, 83+AH Fire Rated Battery, aka BAT-0122, PWHRL12330W4FR, Equal to C&D UPS12-350FR.................................................... 10% OFF PLUS FREE FRT FOR QTY 36+
CSB HRL12330WFR CSB 12VDC, 83+AH Fire Rated Battery, aka BAT-0122, PWHRL12330W4FR, Equal to C&D UPS12-350FR.................................................... 10% OFF PLUS FREE FRT FOR QTY 36+
 
Alternative Views:


List Price: $269.95
Our Price: $209.33
You save $60.62!
TYPE 9

Product Code: HRL12330WFR-F
Qty:

Description
 
  • UL1778, Female M6 terminal, Hardware included
  • DIMS = 12.15in X 6.65in X 8.44in H

    The HRL12330WFR is a certified 10 year replacement battery and has a full 3 year replacement warranty. It is specially designed for high efficiency discharge applications including use with uninterruptible power systems. It is rated at more than 260 cycles at 100% discharge in cycle service, up to 10 years in standby service. Most major UPS suppliers certify CSB batteries and provide them as standard emergency power sources.

    PLEASE CALL FOR AVAILABILITY

    Free freight for quantity 36+
    Please allow 3-5 days to ship
Specifications
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 330W @15 minute-rate to 1.67V per cell @25℃ (77°F)
Weight Approx. 29.6 kg (65.26 lbs)
Maximum Discharge Current 800A (5sec)
Internal Resistance Approx. Approx. 4mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25℃±3℃ (77°F±5°F)
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25℃ (77°F)
Recommended Maximum Charging Current Limit 33A
Equalization and Cycle Service 14.4 to 15.0 VDC/Unit Average at 25℃(77°F)
Self Discharge CSB Batteries can be stored for more than 6 months at 25℃(77°F). Please charge batteries before using. For higher temperatures the time interval will be shorter.
Terminal I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Container Material Polypropylene(UL 94-V0/File E50955)*Flammability resistance of (UL 94-HB/File E216959) can be available upon request.

Dimensions


Constant Current Discharge Characteristics Unit:Amperes (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 20MIN 30MIN 40MIN 45MIN 50MIN 60MIN 90MIN
1.60V 383.00 260.00 201.00 165.00 123.00 98.40 89.90 82.00 70.20 52.10
1.67V 338.50 239.10 187.90 156.80 116.60 94.20 85.30 78.10 67.10 49.40
1.70V 318.30 229.00 180.90 152.40 113.30 91.10 83.40 76.40 64.90 47.30
1.75V 284.20 210.00 168.40 144.40 106.00 85.60 78.94 72.50 61.23 44.40
1.80V 253.10 193.30 158.12 135.00 98.40 79.60 72.46 66.37 56.62 41.60
1.85V 219.00 177.00 146.89 125.02 92.46 74.90 68.48 62.51 53.45 39.50
Constant Power Discharge Characteristics Unit:Watts (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 20MIN 30MIN 40MIN 45MIN 50MIN 60MIN 90MIN
1.60V 4044.00 2772.00 2148.00 1770.00 1320.00 1062.00 972.00 888.00 762.00 566.40
1.67V 3621.00 2608.00 2040.00 1712.00 1290.00 1032.00 936.00 864.00 744.00 547.20
1.70V 3438.00 2520.00 1979.00 1679.00 1266.00 1008.00 924.00 852.00 726.00 528.60
1.75V 3115.00 2354.00 1891.00 1605.00 1210.00 963.00 894.00 816.00 696.00 503.40
1.80V 2791.00 2180.00 1795.00 1528.00 1144.72 918.00 833.10 762.00 650.27 483.60
1.85V 2478.00 2016.00 1690.44 1428.00 1070.03 864.00 785.77 720.00 613.33 459.60